RUSHIL DECOR

Hospital walls and washrooms: what NHS design guidance asks of surfaces, and where compact fits

Health Building Note 00-10 sets out what the walls, ceilings and sanitary assemblies of healthcare buildings should be made of. Read clause by clause, its requirements describe a compact laminate.

6 min readUpdated Oct 22, 2026

In short

  • England's Health Building Note 00-10 asks for clinical walls and sanitary panels that are smooth, hard, seamless and impervious, resist detergents, disinfectants and knocks, and give microbes nothing to grow on.
  • VAULT compact answers each point in its data sheet: a 0.4 % mass gain in boiling water against 2 %, grade 5 in all EN 438 staining groups, no fungal growth to ASTM G21 and more than 99.99 % reduction of bacteria and viruses.
  • It also takes an 1800 mm impact drop, and as a solid panel with no edge banding it suits pre-plumbed assembly panels. These are test results, not a declaration of conformity.
Public washroom with a long row of wood-décor compact cubicles in black frames opposite a basin counter
VAULT compact cubicles. In healthcare, HBN 00-10 asks for walls and sanitary panels that are smooth, seamless and impervious.Image: Rushil Decor, VAULT catalogue

How this guide was put together

This guide reads Health Building Note 00-10, published by the Department of Health in England in 2013 for the design of healthcare buildings: Part B on walls and ceilings and Part C on sanitary assemblies. It sets Rushil's VAULT data sheet against the requirements and adds a laboratory study of hospital surfaces from Baylor University, reviewed in more detail elsewhere on this site. The guidance is written for England and is widely used as a reference beyond it; meeting it is a matter for each project and its infection prevention team, and this article makes no compliance claim.

Smooth, hard, seamless, impervious

The guidance starts from cleaning. All finishes in healthcare buildings should be chosen with cleaning in mind, especially where blood or body fluids may be present, which means smooth, non-porous and water-resistant surfaces. In clinical areas, Part B asks for smooth, hard, seamless and impervious surfaces, and wall surfaces free from fissures, open joints or crevices. Wall finishes must be impermeable, easy to wipe over and not physically affected or degraded by detergents and disinfectants.

Sanitary assemblies get the same treatment. Part C asks that the panels of pre-plumbed assemblies, the boxed-in units that carry basins, WCs and their pipework, be easy to clean, durable and impervious.

No foothold for microbes, no damage from knocks

Two further clauses go beyond cleaning. Wall finishes should not be made of materials that promote or sustain the growth of fungi and microorganisms. And they should be durable enough to withstand minor impacts without additional wall protection; where protection is needed, the fittings listed include protective plates and sheeting alongside handrails, crash rails and corner guards.

What VAULT's data sheet reports

Rushil's VAULT compact, made for cubicles, partitions and wet, high-traffic interiors, answers these clauses with test results. Its surface is impervious: after immersion in boiling water the panel gained 0.4 % in mass and in the moisture test 0.2 %, against limits of 2 %. Staining was graded 5, no visible change, in all three EN 438 staining groups. In the ASTM G21 fungal test it scored 0, no growth, and in the JIS Z 2801 and ISO 21702 tests its surface reduced bacteria and viruses by more than 99.99 %. In the large-ball impact test it took a 1,800 mm drop with an indentation of no more than 10 mm.

Because compact is solid through its thickness, a cubicle or wall panel needs no edge banding that could open up, and large sheets keep joints few. These are test results, not a declaration of conformity.

Seamless
HBN asks for smooth, hard, seamless and impervious surfaces in clinical areas
HBN 00-10 B
0
fungal growth on VAULT in the ASTM G21 test
Rushil TDS
1,800 mm
VAULT large-ball impact drop height; indentation no more than 10 mm
Rushil TDS
Grade 5
VAULT staining in all three EN 438 groups
Rushil TDS
> 99.99 %
bacterial reduction on VAULT to JIS Z 2801
Rushil TDS
1.7 %
change in HPL roughness after six simulated years of wear
Harris 2020
Healthcare surfaces in six numbers.Diagram drawn for this site from the figures in the article

What the research adds

Laboratory research points the same way. At Baylor University, HPL was tested beside stainless steel, acrylic solid surface and two copper-based materials. Its surface roughness changed by 1.7 % after abrasion simulating six years of wear, the smallest change of the five, and two hospital disinfectants eradicated MRSA on it as reliably as on steel. Twenty-four hours after inoculation, no MRSA was found on HPL, while stainless steel and the acrylic solid surface still carried colonies. The work was done on laboratory samples.

What this means for hospitals and clinics

Read clause by clause, HBN 00-10 asks for walls and sanitary panels that are smooth, seamless and impervious, that resist detergents, disinfectants and knocks, and that give microbes nothing to live on. VAULT compact meets that description with published test results for every point, and its large sheets and solid edges keep the joints and crevices the guidance warns against to a minimum.

For cubicles, pre-plumbed assembly panels, wall cladding and protective sheeting in corridors, wards and washrooms, VAULT is the product to sample. Involve the infection prevention team early, as the guidance asks; samples and the full data sheet are available on request.

Common questions

What does HBN 00-10 ask of wall surfaces in clinical areas?

Smooth, hard, seamless and impervious surfaces, free from fissures, open joints or crevices, that are easy to wipe, not degraded by detergents and disinfectants, do not support fungal or microbial growth and withstand minor impacts.

How does VAULT compact match those requirements?

Its data sheet reports a 0.4 % mass gain in boiling water, grade 5 for all EN 438 staining groups, no fungal growth in ASTM G21, more than 99.99 % bacterial and viral reduction and a 1,800 mm impact drop. These are test results, not a declaration of conformity.

Can compact be used for pre-plumbed assembly panels?

HBN 00-10 Part C asks for panels that are easy to clean, durable and impervious. Compact HPL is solid, water-resistant and needs no edge banding, which suits that use; confirm the detail with the assembly maker and the infection prevention team.

Sources

  1. Department of Health, Health Building Note 00-10 — Part B: Walls and ceilingsJan 1, 2013 · en
  2. Department of Health, Health Building Note 00-10 — Part C: Sanitary assembliesJan 1, 2013 · en
  3. HERD: Health Environments Research & Design Journal 14(1), Harris D., Taylor K. P., Napierkowski K., Zechmann B. — Indoor Finish Material Influence on Contamination, Transmission, and Eradication of Methicillin-Resistant Staphylococcus aureus (MRSA)Aug 31, 2020 · en
  4. Rushil Decor — VIR VAULT (CGS / CGF) — Product Data Sheeten

Compiled for this site from the publications listed above. Summaries are in our own words, not quotations — read the originals for the full argument.

Technical data is based on manufacturer documentation and applicable test reports. Product specifications may vary by grade, thickness, décor, manufacturing batch or application. Please request the latest technical documentation before final specification or installation.