Exterior compact for ventilated façades: reading the weathering data

Exterior compact is a different product from interior compact, not the same panel with a different label. Three things decide whether a specification is sound.

6 min readUpdated Aug 13, 2026

In short

  • Exterior compact is a different product from interior compact: KLADS carries a UV film thicker than 50 µm over decor paper with a lightfastness above 5, on one face or both.
  • After 3 000 hours of artificial weathering to EN 438-2 it keeps appearance grade 5 and a grey-scale contrast of 4–5, against required values of 4 and 3.
  • A 4330 mm panel moves about 2 mm over a 70 °C temperature swing, so the fixings must allow for it — and the façade is assessed as a system, not as a panel.
Building façade clad in wood-effect exterior panels with dark window frames
Exterior compact in a wood decor: the decor sits under a UV film, and the panel has to be free to move.Image: Rushil Decor, KLADS catalogue

One face exposed, or two

The first decision on an exterior panel is how much of it the weather can see, because that determines the UV protection configuration.

On a ventilated façade the outer face is exposed and the inner face sits in the cavity, so single-sided UV protection is the normal specification. On a balcony balustrade, a parapet or a louvre, both faces are exposed and double-sided protection is required. Getting this wrong is not immediately visible — it shows up two or three years later as differential fading between the faces.

The protection itself is a UV film thicker than 50 µm over a decor paper with a lightfastness above 5. Both parts matter: the film slows the ultraviolet, the paper determines what happens to the colour once it gets through.

What the weathering results mean

Two accelerated tests carry the exterior specification. Artificial weathering to EN 438-2 section 29 runs 3 000 hours and returns a grey-scale contrast of 4–5 and an appearance grade of 5, against requirements of 3 and 4. UV resistance to section 28 runs 1 500 hours with the same results.

Accelerated weathering compresses years into weeks under controlled conditions. It is a comparative measure, not a prediction of service life, and it says nothing about a specific orientation, altitude or pollution load. Use it to compare products, not to promise a client a number of years.

Thermal movement drives the fixing design

A coefficient of linear thermal expansion of 6.81 × 10⁻⁶ mm/mm °C sounds small until it is multiplied by a 4330 mm panel and a 70 °C swing between a winter night and a dark panel in summer sun. That is roughly 2 mm of movement along the panel.

The panel has to be allowed to move. Fixing holes are oversized, fixings are located to control where movement is taken up, and joints are dimensioned for the closed and open condition. A façade detailed as if the panel were dimensionally static will telegraph its fixings within a year.

Climate shock testing to EN 438-2 section 19 backs this up: after cycling, appearance holds at grade 5 and the flexural strength and modulus ratios come back at 0.98 and 0.95 against a required 0.95.

≤ 500 mm≤ 700 mm
Fixed point: the hole matches the fastener and carries the panel
Sliding points: holes about 3–5 mm larger than the fastener
Typical maximum centres for an 8 mm panel, after BibLus. The panel moves away from its fixed point.
One fixed point per panel; every other hole is oversized so the panel can expand and contract.Diagram drawn for this site from the figures in the article

The panel is not the façade

This is the point worth being blunt about. Every figure above describes a panel. A ventilated façade is a system — substructure, brackets, cavity, insulation, cavity barriers, fixings — and it is the system that is assessed for fire and for wind load.

Panel test data is a necessary input to that assessment and never a substitute for it. When a supplier presents panel classification as though it settled the façade question, that is the moment to ask what system testing exists.

Mechanical figures for the wind load calculation

Exterior compact is tested in both directions, because it is not isotropic. Bending strength is 136.1 MPa parallel to the long side and 98.8 MPa parallel to the short side; modulus of elasticity is 15 336 and 11 088 MPa respectively. Panel orientation is therefore a structural decision, not only a visual one. Tensile strength is 120 MPa against a required 60, and all values were measured on 6 mm panels.

Common questions

What is the difference between single-sided and double-sided UV protection?

Single-sided carries the UV film on one face, for applications where only that face is exposed — ventilated façades and wall cladding. Double-sided carries it on both, for balcony panelling, parapets and louvres where both faces see sunlight and weather.

How long will an exterior compact façade last?

No responsible answer to that exists as a single number. Accelerated weathering results compare products under controlled conditions; actual service life depends on orientation, exposure, pollution, cleaning regime and installation quality. Ask for the current warranty terms for your territory rather than relying on a general figure.

Can exterior panels be cleaned with a pressure washer?

Rinsing with clean water is the recommended method. High-pressure jets should not be directed close to panel edges or joints, where they can drive water into the build-up.

Written for this site from manufacturer test reports. Not reproduced from any other source.